GW33 series high frequency UPS (three-input and three-output 10K-200K)

GW 3P/3P provides up to 1.0 output power factor, providing higher performance and efficiency for critical applications. This powerful online series integrates true double conversion design, DSP technology and active input power factor correction design to ensure better output voltage, power quality and performance at all times, LCD display provides real-time UPS status, enhanced flexibility to meet the growing power needs of IT and network environments.

Product Features

  • True double conversion online uninterruptible power supply system

  • DSP technology ensures high performance

  • Output power factor

  • Active power factor correction

  • 50/60hz frequency conversion mode

  • ECO energy-saving operation function

  • Emergency power-off function (EPO)

  • Optional parallel function

  • Intelligent charging design to optimize battery performance 

  • Built-in maintenance bypass switch

  • Adjustable number of battery cells

Application Field

  • Information industry

  • IT industry

  • Financial industry

  • Aerospace

  • Industry

  • Computer

  • Communication

  • Data network center


Product Selection

Model

Power

Size (Width * depth * height)

Weight (kg)

GW33-10KL

10KVA/8KW

405*656*817mm

120

GW33-15KL

15KVA/12KW

405*656*817mm

145

GW33-20KL

20KVA/16KW

405*656*817mm

193

GW33-30KL

30KVA/24KW

405*656*941mm

225

GW33-40KL

40KVA/32KW

432*821*1159mm

278

GW33-60KL

60KVA/48KW

432*821*1159mm

365

GW33-80KL

80KVA/64KW

554*975*1286mm

471
GW33-100KL100KVA/80KW554*975*1286mm573
GW33-120KL120KVA/96KW635*975*1326mm650
GW33-160KL160KVA/128KW705*1051*1646mm760
GW33-200KL200KVA/160KW705*1051*1646mm790

*Current specifications and dimensions are subject to change without prior notice.



Technical Parameter


Phase3Phase in/3Phase out
Input 
Rated voltage3x380 / 400 VAC (3Ph+N)
Acceptable voltage range165VAC~280VAC(Ph-N);285VAC~485VAC(Ph-Ph)
Frequency50-60Hz±10%
Inverter
AdmissiblePower Factor0.6-1
AdmissibleCrest factor3:01
Admissibleoverload110%~150%10min~60sec
LimitingHigh overload, short circuit: effective value voltage limit; peak factor current: peak voltage limit
Dynamic recovery time3 cycles
Frequency50/60Hz
Unbalanced output voltage/100% unbalanced load<1%
Maximum sync speed±1Hz/s
Rated voltage3x380/400/415VAC(3Ph+N)
Phase120°±1% (balanced load)
AccuracyStatic: ±1%, Temporary: ±5%
Total harmonic distortion (THDV)<2% linear load
Waveformpure sine wave
Static bypass
Activation criteriamicroprocessor controlled
Allow overload0~150% continuous working; 150-180%60min; >180%5min
Frequency50/60Hz±10%
Transfer againAutomatically after the alarm is cleared
Transfer timeZero
Transfer to bypassImmediately, for over 160% overload
Typesolid state
Voltage176VAC-264VAC(Ph-N); 304VAC-456VAC(Ph-Ph)
Bypass maintenance
Frequency50/60Hz
Overall efficiencybattery mode90%91%92%92%93%
Overall efficiencyline mode89%90%91%91%92%
Typeuninterrupted
Voltage3x400VAC(3Ph+N)
Batteries and chargers
Charging methodCC/CV
Charging voltage432VDC
Rated battery voltage384VDC
Accuracy±1%
Battery type and quantity12VDCX32PCS
recharging current10A